Ethernet Modbus TCP Three Phase Power Quality Analyzer ME537 32GB Data Logger Rogowski Coil Electric Energy AnalyzerAR
SPECIFICATIONS
Accuracy Class: 0.2%
Application: Industrial, IOT, Household, Telecommunication, Electric Power
Basic Current: 100A 300A 600A 1000A 3000A 6000A
Battery Included: no
Brand Name: ZUIDID,MEATROL
Communication protocol: MODBUS TCP and MODBUS-RTU
Current sensor: Rogowski coil/ 333mV CT
Dimensions: 96*96*94mm
Display: 3.5 inch IPS display
Display Type: Digital Only
Feature: Safety, Waterproof, Led Display, Light Weight, Eco-Friendly, Durable, Time Display
Frequency: 45Hz-65Hz
High-concerned chemical: none
Max. Current: 18000A
Measurement category: CAT III 600V
Measuring Energy Range: 1.0 x 10^9 kwh
Model Number: ME537
Operating Temperature: -20℃~+55℃
Origin: Mainland China
Output Voltage: 85 - 305VAC/100 - 430VDC
Phase: Three Phase
Place of Origin: Shanghai, China
Primary current: 1-99999A
Product name: Panel type Power quality analyzer
Quality level: High quality, Touch button
Rated Current: 100A 300A 600A 1000A 3000A 6000A
Type: Three phase / Single phase
Voltage range: 0-600VAC
Contact US:

* Support systems of single-phase and three-phase. It can measure multiple electrical parameters such as current, voltage, power factor, power, energy, and power quality parameters including harmonic, unbalance degree, voltage swell and voltage dip, etc.
* In addition to the measurement function, ME537 is equipped with various records, such as waveform records and programmable interval measurement value records. To store and record data, it is internally embedded 32 GB memory card.
* Standard RJ45 Ethernet and RS485 communication interfaces, compatible with various configuration systems through standard Modbus TCP and Modbus RTU protocols, transmit real-time electrical parameters collected by the front-end to the system data center.

|
Product name
|
|
|
||
|
Model No.
|
ME537
|
|
||
|
Type
|
Three phase power quality analyzer
|
|
||
|
Application field
|
|
|
||
|
Application field
|
Power analysis, Power measurement, Power quality analysis
|
|
||
|
Wiring mode
|
|
|
||
|
Wiring system
|
3P4W_4CT
3P4W_3CT 3P3W_3CT 3P3W_2CT 1P3W 1P2w |
|
||
|
Current sensor
|
Rogowski coil
Voltage-output current clamp |
|
||
|
Voltage access
|
Direct access
Connected through voltage transformer |
|
||
|
Storage
|
|
|
||
|
Type
|
TF card
|
|
||
|
Capacity
|
32GB
|
|
||
|
Data export
|
U disk export (U disk file is FAT32 system)
|
|
||
|
Communication
|
|
|
||
|
Interface
|
RJ45- Ethernet
|
RS485
|
||
|
Protocol
|
Modbus-TCP
|
Modbus-RTU
|
||
|
Power Supply
|
|
|
||
|
Power
|
85 - 305VAC/100 - 430VDC
|
|
||
|
Maximum power consumption
|
5VA
|
|
||
|
Display
|
|
|
||
|
Size
|
3.5 inch
|
|
||
|
Type
|
IPS display
|
|
||
|
Resolution ratio
|
480*800
|
|
||
|
Machinery
|
|
|
||
|
Dimention
|
96*96*94mm
|
|
||
|
Weight
|
850g
|
|
||
|
Environment
|
|
|
||
|
Working environment
|
Temperature-20℃~+55℃, Humidity below 90% RH
|
|
||
|
Storage environment
|
Temperature-40℃~+70℃, Humidity below 95% RH(non-condensing)
|
|
||
|
Altitude
|
≤2km
|
|
||
|
Measurement category
|
CAT III 600V
|
|
||
|
IP code
|
IP30
|
|
||
|
Real-time measurement data
|
|
|
|
Voltage
|
Phase voltage: Phase ABC
N phase to ground voltage Line voltage: UAB, UBC, UCA Voltage peak coefficient: Phase ABC Voltage peak: Phase ABC |
|
|
Current
|
Phase current: Phase ABCN
Current peak coefficient: Phase ABC K Factor: Phase ABC |
|
|
Frequency
|
Line frequency
|
|
|
Power
|
Active power: Phase ABC and total
Reactive power: Phase ABC and total Apparent power: Phase ABC and total |
|
|
Power factor
|
Phase ABC and total
|
|
|
Fundamental harmonic power factor
|
Phase ABC and total
|
|
|
Electrical energy
|
Active Energy: Phase ABC and total (import / export)
Reactive energy: Phase ABC and total (import / export) Apparent Energy: Phase ABC and total CO2 emissions |
|
|
Harmonic measurement data
|
|
|
|
Voltage harmonics
|
THD (Total harmonic percentage), TOHD (Odd total harmonic percentage), TEHD (Even total harmonic percentage), phase ABC 1-50th
harmonic percentage, phase ABC 1-50th harmonic voltage value |
|
|
Current harmonics
|
THD (Total harmonic percentage), TOHD (Odd total harmonic percentage), TEHD (Even total harmonic percentage), phase ABC 1- 50th
harmonic percentage, phase ABC 1-50th harmonic current value |
|
|
Waveform
|
|
|
|
Voltage waveform
|
Phase ABC voltage waveform or UAB, UBC, UCA line voltage waveform
|
|
|
Current waveform
|
Phase ABC current waveform
|
|
|
Phase angle
|
|
|
|
Voltag pehase angle
|
Phase ABC
|
|
|
Current pehase angle
|
Phase ABC
|
|
|
Phase angle between voltage and current
|
Phase ABC
|
|
|
Unbalance
|
|
|
|
Unbalance
|
Voltage unbalance, current unbalance
|
|
|
Demand
|
|
|
|
Power demand and peak demand
|
Phase ABC active power and total power, phase ABC reactive power and total power, phase ABC apparent power and total power
|
|
|
Current demand and peak demand
|
Phase ABC
|
|
|
Parameter
|
Type
|
Description
|
|
Voltage
|
Channel input voltage range
|
0-600VAC
|
|
|
Measurement range
|
0-600VAC
|
|
|
Measurement accuracy
|
0.2%
|
|
Current
|
Channel input voltage range
|
0-420mVAC
|
|
|
Measurement range
|
Different current sensors have different measuring ranges
|
|
|
Measurement accuracy
|
0.2%+ Accuracy of current sensor
|
|
Frequency
|
Measurement range
|
45Hz-65Hz
|
|
|
Measurement accuracy
|
±0.001Hz
|
|
Power factor
|
Measurement range
|
-1-+1
|
|
|
Measurement accuracy
|
±0.005
|
|
Power
|
Active power accuracy
|
0.5%
|
|
|
Reactive power accuracy
|
1%
|
|
|
Apparent power accuracy
|
0.5%
|
|
Energy
|
Active energy accuracy
|
0.5%
|
|
|
Reactive energy accuracy
|
1%
|
|
|
Apparent energy accuracy
|
0.5%
|
|
Data record
|
|
|
|
Record name
|
Settable
|
|
|
Record start time
|
Settable
|
|
|
Record duration
|
Selectable
|
|
|
Recording interval
|
Settable
|
|
|
Basic data record
|
Phase voltage
Line voltage Current Frequency Power factor Fundamental harmonic power factor Power(Active, Reactive, Apparent) Active Energy (Import energy, Export energy) Reactive energy (Import energy, Export energy) Apparent Energy Voltage harmonics (Total harmonic, odd total harmonic, even total harmonic) Current harmonics (Total harmonic, odd total harmonic, even total harmonic) Phase voltage peak Peak factor of phase voltage Current crest factor Current K factor Voltage unbalance (negative sequence, zero sequence) Current unbalance (negative sequence, zero sequence) Angle (phase voltage angle, phase current angle, angle between voltages, angle between currents, angle between voltages and currents) Max min (Phase voltage, Line voltage, Current, Frequency, Power factor, Fundamental harmonic power factor, Active power, Reactive power, Apparent power) Demand (Current, Active power, Reactive power, Apparent power) Peak Demand (Current, Active power, Reactive power, Apparent power) |
|
|
Voltage harmonic data record
|
Voltage harmonics (Total harmonic distortion THD, Odd total harmonic TOHD, Even total harmonic TEHD, 1-50th Harmonic percentage
and voltage value) |
|
|
Current harmonic data record
|
Current harmonics (total harmonic distortion THD, Odd total harmonicTOHD, Even total harmonic TEHD, 1-50th Harmonic percentage and
current value) |
|
|
Data storage format
|
CSV
|
|
|
Event record [[1]]
|
|
|
|
Recorded data
|
Event type
Start time Duration Amplitude value |
|
|
Data storage format
|
CSV
|
|
|
Waveform recording
|
|
|
|
Record name
|
Settable
|
|
|
Record the start time
|
Settable
|
|
|
Record the duration
|
Settable
|
|
|
Sampling rate
|
Settable
|
|
|
Logged data
|
Phase ABC voltage waveform
Phase ABC current waveform |
|
|
Data storage format
|
CSV
|
|





- Standard Shipping: Standard Shipping (12–18 Business Days)
- Express Shipping: Expedited Shipping (5–9 Business Days)
- Free Shipping: Orders over $199 qualify automatically
- Tracking: Full tracking number provided for all orders
- Returns: 30-day hassle-free return window
- Condition: Items must be unused and in original packaging
- Refund: Full refund processed within 3-5 business days
- Factory Direct: ISO/TS 16949 certified manufacturer
- Quality: 100% electrical continuity tested before shipment
- Experience: 15+ years in automotive connector industry
- Support: Professional technical support available
You may also like
Blog posts
Title
Subscribe to our emails
Be the first to know about new collections and special offers.