UV Flame Detector QRA2 QRA2M Compatible OEM & Replacement Parts Boiler Burner UV Probe Photocell Electric Eye Spare Parts

UV Flame Detector QRA2 QRA2M Compatible OEM & Replacement Parts Boiler Burner UV Probe Photocell Electric Eye Spare Parts

QRA2M Bulb - CN
$203.13
Sale price  $203.13 Regular price  $0.00
Skip to product information
UV Flame Detector QRA2 QRA2M Compatible OEM & Replacement Parts Boiler Burner UV Probe Photocell Electric Eye Spare Parts
UV Flame Detector QRA2 QRA2M Compatible OEM & Replacement Parts Boiler Burner UV Probe Photocell Electric Eye Spare Parts
$203.13
Sale price  $203.13 Regular price  $0.00
Color
Description

SPECIFICATIONS

Brand Name: NONE

High-concerned chemical: none

Origin: Mainland China



QRA2 and QRA2M series UV flame detectors are dedicated OEM flame monitoring spare parts for natural gas, LPG and methanol burners. Equipped with professional ultraviolet induction chip, the probe only captures ultraviolet spectrum generated by gas and methanol flame, effectively isolating interference from workshop LED lamps, incandescent lights and ambient natural light to prevent false flameout alarms.
QRA2 is standard short probe for small and medium compact gas burners; QRA2M extended long probe fits deep cavity combustion heads and large industrial gas kilns. After successful ignition, the detector continuously transmits stable UV flame signal to the program controller to maintain normal fuel supply. If accidental flame loss happens during running, the UV photocell instantly cuts off signal output and triggers safety interlock to close gas valve, eliminating risks of fuel leakage and deflagration.
Unified external fixing thread, integrated signal wire and plug terminal fully match original installation structure. Users can directly replace aging, carbon-fouled and low-sensitivity old UV probes without modifying burner internal wiring and mounting brackets. High temperature resistant quartz lens blocks oil mist and carbon deposit, guaranteeing long-term stable detection performance under high temperature boiler environment.

Core Technical Specs

  • Complete Models: QRA2, QRA2M

  • Matching Equipment: Natural gas, LPG, methanol single/two-stage industrial burners

  • Sensing Core: Special UV sensitive chip, only identify flame ultraviolet rays, immune to visible light interference

  • Optical Lens: High temperature anti-fog quartz lens, easy to wipe oil stains and carbon dust

  • Housing Material: Rust-proof metal shielding shell, stable under long-term thermal radiation

  • Working Ambient Temperature: -20℃ ~ +95℃

  • Mounting Mode: Standard outer fixing thread, one-piece plug signal cable

  • Detection Function: Real-time UV flame signal feedback, automatic safety shutdown upon flameout

  • Compliance Standard: EN676 gas burner safety specification, CE certified

Core Advantages

  1. Exclusive UV induction chip design, no false alarm caused by indoor lighting and sunlight interference

  2. Short and long two size options to meet different burner cavity depth and installation space requirements

  3. High temperature quartz lens can be cleaned regularly to solve signal attenuation failure from long-term oil fume accumulation

  4. Metal shielding housing strengthens anti-electromagnetic interference ability, reliable detection in complex factory workshop environment

  5. 1:1 OEM consistent installation dimension and wiring structure, plug-and-play replacement without rewiring

  6. Ultra-fast flameout response speed, instant fuel cut-off interlock protection to avoid gas explosion and leakage hazards

Installation Guidance

  1. Cut off the whole burner power supply and wait for the combustion head to cool down completely

  2. Unplug signal wire plug of old UV detector, unscrew fixing thread and remove aged insensitive probe

  3. Clean oil mist and carbon residue inside burner detection mounting hole

  4. Screw new QRA2/QRA2M UV flame detector tightly into reserved detection seat, align quartz lens toward flame combustion zone

  5. Reconnect signal plug to corresponding terminals of program controller

  6. Power on ignition test; stable flame signal displays after successful ignition. Simulate flame loss, equipment will rapidly trigger safety lockout protection

Application Scope

Universal OEM replacement UV flame safety detection parts for gas and methanol combustion equipment; widely used in gas heating boilers, low-nitrogen steam boilers, methanol furnaces, food drying kilns, textile setting furnaces and industrial heat treatment furnaces burner safety interlock system maintenance replacement.


Free Shipping Over $199
  • Standard Shipping: Standard Shipping (12–18 Business Days)
  • Express Shipping: Expedited Shipping (5–9 Business Days)
  • Free Shipping: Orders over $199 qualify automatically
  • Tracking: Full tracking number provided for all orders
30-Day Return Policy
  • Returns: 30-day hassle-free return window
  • Condition: Items must be unused and in original packaging
  • Refund: Full refund processed within 3-5 business days
Why Choose Us?
  • Factory Direct: ISO/TS 16949 certified manufacturer
  • Quality: 100% electrical continuity tested before shipment
  • Experience: 15+ years in automotive connector industry
  • Support: Professional technical support available
Secure Payment Latest encryption technology
Money-Back Guarantee 30-day hassle-free returns
Quality Assured Factory certified products
Global Fast Shipping Worldwide express delivery

You may also like

Contact us

Subscribe to our emails

Be the first to know about new collections and special offers.